Description
DC Supply
CONTINUOUS VOLTAGE RATING
8 V to 35 V DC continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 10 V. This is achieved without the need for internal batteries. Backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
200 mA at 12 V, 120 mA at 24 V
MAXIMUM STANBY CURRENT
65 mA at 12 V, 35 mA at 24 V
CHARGE ALTERNATOR EXCITATION / FAIL RANGE
0 V to 35 V
Voltage Measurement
NUMBER
2
MEASUREMENT INPUTS
3 Phase + Neutral
Remote Start Controller: Generator Only
Automatic Mains (Utility) Failure Controller: Generator and Mains (Utility)
VOLTAGE RANGE
FREQUENCY RANGE
3.5 Hz to 75 Hz
RESOLUTION
ACCURACY
±1 % Phase to Neutral
±2 % Phase to Phase
±0.05 Hz
Current Transformer Measurement
NUMBER
3
MEASUREMENT INPUTS
Remote Start Controller: Generator Only
Automatic Mains (Utility) Failure Controller: Generator or Load
CURRENT RANGE
0 A to 5 A
RESOLUTION
0.5 %
ACCURACY
±1 %
Inputs
ANALOGUE
Number: 3
Type: Negative Switching Digital Input, Resistive Analogue Input, Current Analogue Input or Voltage Analogue Input
DIGITAL
Number: 4
Type: Negative Switching Digital Input
MAGNETIC PICK-UP INPUT
Voltage Input Range: 0.5 VPeak to 70 VPeak
Frequency Input Range: 1 Hz to 10 kHz
Outputs
DIGITAL
Number: 6
Type: Positive Switching DC Outputs
AUXILIARY SUPPLY OUTPUT
Number: 1
Rating: 20 mA at 5 V
Communications
USB B
1 Programming Port
CAN
1 CAN Port
RS485
1 Fully Isolated RS485 Port (G4501-01 Only)