The DSE4620 is a compact Auto Mains (Utility) Failure Control Module that has been developed to provide an outstanding range of features within a compact enclosure.
140 mm x 113 mm x 43 mm (5.5” x 4.4” x 1.5”)
PANEL CUTOUT SIZE
118 mm x 92 mm (4.6″ x 3.6″)
MAXIMUM PANEL THICKNESS
8.0 mm (0.3”)
WEIGHT
0.28kg
PRODUCT VARIANTS
4620-03 – 4620 Auto Mains (Utility) Failure Control Module (Mpu,Ct,Rtc)
DC SUPPLY
CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking.
MAXIMUM OPERATING CURRENT
85 mA at 12 V, 96 mA at 24 V
MAXIMUM STANDBY CURRENT
51 mA at 12 V, 47 mA at 24 V
MAXIMUM SLEEP CURRENT
35 mA at 12 V, 32 mA at 24 V
MAXIMUM DEEP SLEEP CURRENT
<10 uA at 12 V, <10 uA at 24 V
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V AC (Ph – Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
OUTPUTS
OUTPUT A (FUEL)
10 A short term, 5 A continuous,
at supply voltage
OUTPUT B (START)
10 A short term, 5 A continuous,
at supply voltage
AUXILIARY OUTPUTs C & D
2 A DC at supply voltage
AUXILIARY OUTPUTs E & F
2 A DC at supply voltage
GENERATOR
VOLTAGE RANGE
15 V to 415 V AC (Ph-N)
26 V to 719 V (Ph – Ph)
FREQUENCY RANGE
3.5 Hz to 75 Hz
MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V
FREQUENCY RANGE
10,000 Hz (max)